AIR VELOCITY MEASUREMENT
AIR VELOCITY
MEASUREMENT
Purpose:
To provide a
procedure to measure for airflow velocity and uniformity of velocity and supply
airflow rate in clean room and clean zone.
Scope:
Applicable
to all Air Handling Units system, Forced Air Ventilation system, Laminar Air
Flow system(Unidirectional airflow system), Dynamic pass boxes, Garment
Cubicles, Air showers, Air duct, Non unidirectional airflow
installation(Diffuser, Grills, Risers).
Responsibility:
All HVAC
Engineers.
Definition:
Uniformity of air flow: Unidirectional air flow pattern in
which the point-to-point readings of velocities are within the defined
percentage of the average airflow velocity.
Unidirectional airflow: Controlled air flow through entire
cross section of clean zone with steady velocity and approximately parallel
streamlines.
Non-Unidirectional airflow: Air distribution where the supply
air entering the clean zone mixes with the internal air by means of induction.
Laminar Air flow: Control airflow through the entire
cross section of a clean zone with a steady velocity and approximately parallel
streamline.
Installation: Clean room or one or more clean
zones, together with all associated structures, air handling systems, services
and utilities.
Air change rate: Rate of air change expressed as air
change per unit time and calculated by dividing the volume of air delivered in
the time unit by the volume of the space.
PROCEDURE:
AIR VELOCITY MEASUREMENT IN CLEAN
ROOM HAVING NON UNIDIRECTIONAL AIR FLOW SYSTEM USING ANEMOMETER(VANE TYPE/HOT
WIRE ANEMOMETER)
1.
Switch
ON the system/equipment of which air velocity measurement to be done.
2.
Test
to be conducted atleast 30 minutes after HVAC system has been operated and the
conditions have been stabilized.
3.
Remove
the diffuser/Grill before taking reading if applicable.
4.
Define
the measuring plane perpendicular to the supply airflow and divide the
measuring plane into grid cells of equal area. Individual area should not
exceed approximately 0.4 sq.mt(4 sq.ft).
5.
The
number of measuring points should be the square root of 10 times of area in
square meters but no less than 4 points and at least one point for each
filter.(Refer-ISO 14644-3).
6.
Measurements
should be taken at the center of each grid cell.
7.
Hold
the anemometer(Vane type anemometer or Hot wire anemometer) about 150 mm to 300
mm from filter face for measuring the filter uniformity of velocity.(Ref- ISO
14644-3).
8.
Switch
ON the anemometer.
9.
Hold
the fan or probe of anemometer at each position to ensure a repeatable reading
and allow at least 5 second for each measurement. Note down the average reading
at each position during that period for multiple locations.
10.
Note
down the time required for stabilize or repeatable reading.
11.
Note
down the air velocity readings at supply and return airflow.
12.
Switch
OFF the anemometer.
13.
Switch
OFF the equipment. If required.
14.
The
total supply air flow rate should be evaluated as:
Q=€(Ac X Vc)
Whre, Q=Total airflow rate,
Ac=Area of each cell
Vc=Airflow velocity at
each cell center.
AIR VELOCITY MEASUREMNT IN CLEANROOM
HAVING NON-UNIDIRECTIONAL AIRFLOW USING FLOW HOOD:
1.
Start
the AHU/FAV of which air quantity measurement to be done.
2.
Test
to be conducted at least 30. Min. after HVAC system has been operated and the
conditions have been stabilized.
3.
Assemble
the hood by fixing four supports pole in the four corner of the flexible fabric
frame.
4.
Press
the ON/OFF key on the display board to turn ON the power.
5.
Hold
the top of the instrument along the perimeter edge of the diffuser or grill so
as to form a seal. Ensure that there should not be any air leakage or by pass
of air from the perimeter edge of the diffuser or grill.
6.
Ensure
that the arrow marking on the display is showing correct direction of air flow.
7.
When
the side sealing along the perimeter is proper and arrow is correct, press the sample
button on the top of the right handle and wait till beep tone comes.
8.
The
display will show the value of total air quantity.
9.
Note
down the air quantity through the grill or diffuser.
10.
Air
velocity through the grill or diffuser can be calculated as total air quantity
divided by filter area.
11.
For
measuring velocities of Diffuser/Grills, LAF/RLAF above 600 X 600 mm size
Capture Hood/Vane type/Hot wire anemometer to be used.
SUPPLY AIR VELOCITY FLOW EATE IN AIR
DUCTS:
Where anemometer
is used, for a rectangular duct, the measuring plane in the duct should be
divided into grid cells of equal area of minimum of 9 and maximum of 16 and
each cell dimensions should be approximately 0.4 Sq.mt(4 Sq.ft) or smaller then
the airflow velocity should be measured at the center of each grid cell.
Measuring time at each position should be ar least 5 second and ensure for a
repeatable reading. The average values during that period should be recorded.
The total
supply airflow rate should be evaluated as:
Q=€(Ac X Vc)
Whre, Q=Total airflow rate,
Ac=Area of each cell
Vc=Airflow velocity at
each cell center.
AIR CHANGE RATE:
1.
Start
the AHU.
2.
Take
mean velocity reading of each supply grill/diffuser and calculate cfm using
following formula.
CFM=Velocity(ft/min)XArea of grill(ft²).
3.
Calculate
total cfm of grill/ diffuser by adding cfm of each grill/ diffuser
respectively.
4.
Calculate
volume(ft³) of the area.
5.
Calculate
the number of air changes using following formula.
Total cfm
No. of air changes/hr=---------------------------------------X60
Total volume of the area
6. Air
changes should be more than 6 for Area ISO 8, And should be more than 30 for
area ISO 5, ISO 6, And should be more than 20 for areas ISO 7.
AIR VELOCITY MEASUREMENT OF
UNIDIRECTIONAL AIR FLOW SYSTEM USING ANEMOMETER (VANE TYPE/HOT WIRE ANEMOMETER)
1.
Switch
ON the system/equipment of which air velocity measurement to be done. Let the
equipment run for 30 minutes before to stable the system.
2.
Check
the zero setting of Manometer across HEPA filter, adjust if required.
3.
If
the pressure drop is not within the limit, then Switch OFF the system and clean
the pre filter and intermediate filter as per company sop and ensure for the
rectification.
4.
Check
the differential pressure across HEPA filter and the Pre filter.
5.
The
number of measuring points should be the square root of 10 times of area in
square meters but not less than 4 points.
6.
Define
the measuring plane perpendicular to the supply airflow and divide the
measuring plane into grid cells of equal area. Individual area should not
exceed approximately 0.4 sq.mt(4 sq.ft).
7.
The
total filtration area to be considered as one plane and not the individual
filters.
8.
Hold
the anemometer (Vane type anemometer or Hot wire anemometer) about 150 mm to
300 mm from filter uniformity of velocity.(Ref- ISO 14644-3)
9.
Measurements
should be taken at the centre of each grid cell.
10.
Switch
ON the anemometer.
11.
Hold
the anemometer (Vane type anemometer or Hot wire anemometer) at each cell till the anemometer reading
stabilizes or ensures the repeatable reading and at least 5 second for each
measurement.
12.
Note down the time required for stabilize or
repeatable reading.
13.
Note
down the air velocity readings and their corresponding grid identification on a
diagram of clean room or clean zone.
14.
Switch
OFF the anemometer.
15.
Switch
OFF the equipment. If required.
16.
Calculate
the arithmetic mean and the standard deviation(Uniformity) of the airflow
velocity, expressed as a percentage of the mean, as follows:
Standard deviation
Relative standard deviation=--------------------------(100%)
Average velocity
ACCEPTANCE CRITERIA:
1.
Airflow
velocity (Homogenous air speed) should be within the range of 72 to 107 FPM OR
0.36 to 0.54 m/s for Laminar air flow system(unidirectional airflow system) as
per EU guideline.
2.
For
uniformity testing the relative standard deviation should be less than 15%.
3.
If
the velocity readings within the required limit are not observed then open the
damper gradually so as to get desired mean air velocity. Even after opening the
damper velocity is not maintained then an investigation should include review
of status of blower, re filter & HEPA filter motor, damper, etc.,
FREQUENCY FOR AIR
VELOCITY MEASUREMENT:
1.
For
LAF, Dynamic pass box, Unidirectional Air flow installation Garment cubicle
filter face velocity and uniformity to be measured quarterly or if any
modification or as per company norms..
2.
For
AHU of Grade B(ISO 5) to be measured quarterly or earlier if any modification or as per company norms.
3.
For
AHU of Grade C(ISO 7) to be measured six monthly or earlier if any
modifications or as per company norms.
4.
For
AHU of Grade D and ISO 8, to be measured yearly or earlier if any modification or as per company norms.
References:
ISO 14644-3:
Clean rooms and associated controlled environments-Part 3 Metrology and test
methods.
ISO 14644-4:
Clean rooms and associated controlled environments-Part 4 Design to Good
Manufacturing Practice.
Very nice artical...
ReplyDeleteGood afternoon...I am asking about the air velocity measurement for UDAF, do we apply the acceptance critera (0.36:0.54 m/s) for each location or for the average value for the 5 locations?
ReplyDeleteAlso, if we consider that a location has air velocity value above 0.54 m/s and readings of average is within limit, is it accepted or not??
Very efficiently written information. I am definitely enjoying your website. Would you like to get more information about heat ventilation, so just click on this. air exchange ventilation system
ReplyDeleteIf more people that write articles really concerned themselves with writing great content like you, more readers would be interested in their writings. Thank you for caring about your content. Sales velocity calculation
ReplyDelete