Objective:

To demonstrate the capability of AHU to maintain room temperature and relative humidity within the specified design limits.

Acceptance Criteria:

The room temperature and relative humidity shall meet the design values as set for each room.

Test equipment:

Thermo-hygrometers.

Procedure:

1.      Before starting the study ensure that Air conditioning system is in continuous operation for at least 24 hour prior to performing these tests.
2.      In the area the temperature control zone shall be divided into grids of equal area having dimensions of approximately 100 ft²(3m. X 3m. or 9m²). If the area is less than 100 ft²(3m. X 3m. or 9m²) temperature  mapping shall be done at one location.
3.      In small area the temperature monitoring shall be done at single location. If the huge area it can be increased instead of 1 location.
4.      If the storage racks are provided in the area, the number of locations shall be distributed at top, middle and bottom level of racks. No. of temperature locations can be increased as per study requirement .
5.      Monitoring area with no. of locations to be monitored.
6.      Ensure that the measuring instrument is in calibrated state with a valid calibration certificate.
7.      Distribution studies shall be performed at working height level. Monitor the temperature and relative humidity in all critical rooms, area for 3 days with an interval of 30 minutes for mapping with data loggers.
8.      Manually monitor the temperature and relative humidity in all non-critical rooms area for 3 consecutive days considering 3 times a day(During working shifts) with a frequency of 4 hours.